EasyManua.ls Logo

Daikin VRVII - Page 138

Daikin VRVII
385 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Indication on the Remote Controller
133
Remote Controller Display
E9
Applicable Models
VRVII, -WII, -WIII and II-S Series
Method of Error Detection
Check disconnection of connector
Check continuity of electronic expansion valve coil
Error Decision Conditions
Error is generated under no common power supply when
the power is ON.
Supposed Causes
Defective electronic expansion valve coil
Defective outside unit PCB
Defective connecting cable

Table of Contents