EasyManua.ls Logo

Daikin VRVII - J8 Thermistor System Abnormality

Daikin VRVII
385 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Indication on the Remote Controller
178
3.43
J8
Thermistor System
Abnormality
Remote Controller Display
J8
Applicable Models
VRVIII-Q Series
Method of Error Detection
Error is detected according to the temperature detected
by each individual thermistor.
Error Decision Conditions
When thermistor is disconnected or short-circuited during
operation
Supposed Causes
Defective thermistor
Defective connection of connector
Defective outdoor unit PCB (control PCB)

Table of Contents

Related product manuals