EasyManua.ls Logo

Daikin VRVII - H7 Outdoor Unit Fan Motor Signal Abnormality

Daikin VRVII
385 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Indication on the Remote Controller
150
3.33
H7
Outdoor Unit Fan Motor
Signal Abnormality
Remote Controller Display
H7
Applicable Models
VRVIII and III-Q Series
Method of Error Detection
Detection of abnormal signal from fan motor.
Error Decision Conditions
In case of detection of abnormal signal at starting fan
motor.
Supposed Causes
Defective fan motor signal (circuit error)
Broken, short circuited or disconnection connector of
fan motor connection cable
Defective fan Inverter PCB

Table of Contents

Related product manuals