EasyManua.ls Logo

Daikin VRVII - E9 Electronic Expansion Valve Coil Abnormality

Daikin VRVII
385 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Indication on the Remote Controller
130
3.29
E9
Electronic Expansion Valve
Coil Abnormality
Remote Controller Display
E9
Applicable Models
VRVIII, III-S and III-Q Series
Method of Error Detection
Check disconnection of connector
To be detected based on continuity existence of
electronic expansion valve coil
Error Decision Conditions
No current is detected in the common (COM [+]) when
power supply is ON.
Supposed Causes
Disconnection of connectors for electronic expansion
valve
Defective electronic expansion valve coil
Defective outdoor unit main PCB

Table of Contents