EasyManua.ls Logo

Daikin VRVII - Page 178

Daikin VRVII
385 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Indication on the Remote Controller
173
Troubleshooting
Refer to P.369.
NO
YES
Connect the
connector and
turn ON again.
Connector is
connected to outdoor
unit PCB.
NO
Replace the
thermistor.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
Replace the
outdoor unit
PCB.
CHECK 11
CHECK 11

Table of Contents