Troubleshooting by Indication on the Remote Controller
175
Troubleshooting
Refer to P.369.
NO
YES
Connect the
connector and
turn ON again.
Connector is
connected to outdoor
unit PCB.
NO
Replace the
thermistor.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
indoor unit PCB.
Confirm which thermistor
is abnormal using outdoor
unit "monitor mode".
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
Replace the
outdoor unit
PCB.
CHECK 11
CHECK 11