Loading...
Troubleshooting by Indication on the Remote Controller
228
A
NO
YES
The
"LC" error
recurs.
YES
Replace the
control PCB.
Continue the
operation.
(It is supposed
that the error
results from
causes such as
instantaneous
power failure.)
The
micro-
computer normal
monitor (green) of the
inverter PCB is
blinking.
NO
Replace the
inverter PCB.
If the spare
PCB has
significant
damage, the
compressor is
probably get
defective. In
this case, carry
out inspections
on the
compressor
again.