Troubleshooting by Indication on the Remote Controller
236
Note:
1. Measure voltage at the power supply terminal block.
2. Measure voltage at terminals RED, WHITE and
BLACK wire of the diode module inside the inverter
while the compressor is running.
A
Explanation for users
Give the user a copy of
"notification of inspection
results" and leave it up to him
to improve the imbalance.
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.
In accordance with "notification of inspection
results" accompanying spare parts.