Troubleshooting by Indication on the Remote Controller
258
Refer to P.369.
Refer to P.372.
A
NO
Replace the
thermistor.
Replace the
outdoor unit
PCB.
CHECK 11
Resistance
is normal when
measured with the
suction pipe thermistor
and heat exchanger
thermistor disconnected
from the outdoor unit
PCB.
YES
CHECK 11
CHECK 12