Troubleshooting by Indication on the Remote Controller
268
Refer to P.354.
YES
Has the
inverter PCB caused
damage?
Replace the
inverter PCB.
If the inverter
PCB is badly
damaged,
compressor
and fan motor
are likely to
get defective.
NO
A
YES
Stop
(standby) before
the fan rotates.
Replace the
noise filter PCB.
(Defective noise
filter)
NO
YES
Stop
(standby) when
the compressor
startup.
Replace the
inverter PCB.
If the inverter
PCB is badly
damaged,
recheck the
compressor.
NO
YES
The U2 error
recurs.
Check the
harness.
Continue the
operation.
The error may
temporarily
result from
external
factors.
Causes:
Instantaneous
power failure
(open phase),
noises, or else.
NO
Remove and insert the
connectors.
Turn ON the power
supply, and start
operation.
CHECK 4