Troubleshooting by Indication on the Remote Controller
328
Troubleshooting
The
number
of indoor
units connected to
the same refrigerant
circuit system should
not be more than
64 units.
YES
NO
Replace the
outdoor unit main
PCB.
The number of
indoor units
exceeds the
standard. Check
the connection to
correct.
Check if
the refrigerant
type of the outdoor unit
corresponds to that
of the indoor
unit.
YES
NO
Replace the
outdoor unit main
PCB.
Match the
refrigerant types
of the outdoor
unit and the
indoor unit.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Check 3 Check 4
Diagnosis Flow 2
Check 3 Check 4
Diagnosis Flow 1