Troubleshooting by Indication on the Remote Controller
353
Note:
1. Refer to “Low pressure protection control” for hot gas
bypass control.
2. Refer to “Subcooling electronic expansion valve
control”.
3. “Superheating temperature control” in cooling is
conducted by indoor unit electronic expansion valve.
4. Superheating temperature control in heating is
conducted by outdoor unit electronic expansion valve
(EVM).
5. Judgement criteria of superheat operation:
1 Suction gas superheated degree: 10°C and over.
2 Discharge gas superheated degree: 45°C and
over, except immediately after compressor starts up
or is running under drooping control.
(Use the above values as a guide. Depending on the
other conditions, the unit may be normal despite the
values within the above range.)