Troubleshooting by Indication on the Remote Controller
355
When using the digital type of multiple tester, make
measurement in diode check mode ( )
No.
Measuring
point
Judgement
Criteria
Remarks
+–
1P2U
1.2V and more
Due to condenser charge and
so on, resistance
measurement may require
some time.
2P2V
3P2W
4UP2
0.3 ~ 0.7V
5VP2
6WP2
7N3U
8N3V
9N3W
10 U N3
1.2V and more
Due to condenser charge and
so on, resistance
measurement may require
some time.
11 V N3
12 W N3