22 WGZ030D through WGZ200D OMM 1130-2
Table 7
, Continued
Description Default Range PW
Circuit 2 EXV Control Auto Auto, Manual M
See following section; Automatic Adjusted Limits
Low Evap Pressure-Unload M
High Cond Pressure – Unload
Air: 550 psig
Air: 410- - 555 psig
M
High Cond Pressure – Stop
Water: 420 psig
Air: 565 psig
Water: 375 – 435 psig
Air: 425 – 570 psig
M
Evap. Freeze
38.0 °F
Glycol: 17.5 to 42.0°F (R134a,R22, R407C)
°
M
°
°
High Condenser Pressure Stop
(Water-Cooled = Y
260 to 380 psi (R22, R407C)
375 TO 435 psi (R410A)
M
High Condenser Pressure Stop
(Water Cooled = N)
260 to 380 psi (R22, R407C)
425 to 570 psi (R410A)
M
High Condenser Pressure Stop (R134a)
* Phase Voltage Protection N N,Y M
* Ground Fault Protection
Condenser Fans (Water Cooled = N)
Cond Sat Temp Target 100°F 80 to 120°F M
Forced Fan 1 (>75°F)
Forced Fan 2 (>90°F)
Cooling Tower (Water Cooled = Y)
°
°
°
°
°
°
Valve/VFD Control None
None, Valve Set point, Valve Stage, VFD
Stage, Valve SP/VFD Stage
M
Valve Setpoint
°
°
M
Stage Fan Up @ 80% 0 to 100% M
Valve Control Range (Min)
°
°
Maximum Position @
90 °F 0 to 100 °F
M