OMM 1130-2 21
Setpoints
The following parameters are remembered during power off, are factory set to the Default value, and can be
adjusted to any value in the Range column.
The PW (password) column indicates the password level that must be active in order to change the setpoint.
Passwords are as follows:
O = Operator [0100] M = Manager [2001]
Table 7, Setpoints (setpoints with * are set at Daikin Applied factory)
Description Default Range PW
Unit Enable
Off
Off, On
O
*Unit Mode (R22, R407C, R410A Cool Cool, Cool w/Glycol, Ice w/Glycol, Test O
Unit Mode (R134a) Cool Cool, Cool w/Glycol, Heat, Test
Control source
Switches
Keypad, Network, Switches
O
*Available Modes (R22,R407C,R410A) Cool
Cool, Cool w/Glycol, Cool/Ice w/Glycol
Ice w/Glycol, Test
M
*Available Modes (R134a) Cool
Test, Cool, Cool w/Glycol, Cool/Heat, COOL/HEAT
w/Glycol, Heat w/Glycol,
M
Evap LWT
44. 0 °F
Without Glycol: 40.0 to 60.0°F
40.0 to 85.0°F (R134a Only)
With Glycol: 20.0 to 60.0°F (R22,R407C)
10.0 to 60.0°F (R410A)
20.0 to 85.0
°
F (R134a)
O
Ice LWT
40. 0
°
F
15.0 to 40.0
°
F
O
Heat LWT (R134a only)
110.o
°
F
110 to 165
°
F
O
Evap Delta T
10.0
°
F
6.0 to 16.0
°
F
O
Startup Delta T
10.0
°
F
1.0 to 15.0
°
F
O
Stop Delta T
0.5 °F 0 to 3.0 °F
O
Max Pulldown Rate
1.0
°
F
0.5 to 5.0
°
F
M
Evap Recirculate Timer
30
15 to 300 seconds
M
Evap Pump
(Refrigerant = R410a,R134a)
#1 Only
#1 Only, #2 Only, Auto, #1 Prim,
#2 Prim
M
Cond Delta T (R134a only)
20.0
°
F
5.0 to 40.0
°
F
Cond Pump Recirculate Timer
(Water-cooled = Yes)
30 15 to 90 seconds M
Cond Pump
(Water-cooled=Yes & Ref=R410A or R134a
#1 Only #1 Only, #2 Only, Auto, #1 Prim, #2 Prim M
Low Ambient Lockout(Water-Cooled = No)
35.0 °F
35 to 70 °F
If Speedtrol = Yes
-2.0 to70.0°F (R22,R407C)
-10.0 to 70.0 (R410A)
N/A (R134a)
M
Demand Limit
Off
Off, On
M
* Water Cooled
Off
Off, On
M
Ice Time Delay 12 hrs 1 to 23 hrs M
Clear Ice Delay
No
No, Yes
M
Hot Gas Delay Time
30 sec.
30 to 180 seconds
M
BAS Protocol
Modbus
BACnet, LonWorks, Modbus
M
Ident number
001
000-200
M
Baud rate
9600
1200,2400,4800,9600,19200
M
Units
F/psi
F/psi (only)
Language
English
English (only)
* Refrigerant Select
None
R22, R407C, R410A, R134a
Cooling Reset Type
None
None, 4-20mA, [Return( Refrig = R134a only)]
O
Cooling Maximum Reset
10 ºF
0 to 16 ºF
O
Cooling Start Reset Delta T 10 ºF 0 to 16 ºF (Refrig = R134a only) O
Compressor
# of Compressors
(Refrig = R410A or R134a to select 6)
4 4, 6 M
Clear Cycle Tmr
Off
On/Off
M
Stage Up Delay 240 sec 90 to 480 seconds M
Stage Down Delay
30
20 to 60 sec
M
Start-Start
15 min
10 to 60 min
M
Stop-Start
5 min
3 to 20 min
M