64 WGZ030D through WGZ200D OMM 1130-2
# of Compressors = 4 # of Compressors = 6
SET COMP SPs (3)
SET COMP SPs (3)
Comp 1 = Enable
Comp 1 = Enable
Comp 3 = Enable
Comp 3 = Enable
Comp 5 = Enable
# of
Compressors = 4 # of Compressors = 6
SET COMP SPs (4)
SET COMP SPs (4)
Comp 2 = Enable
Comp 2 = Enable
Comp 4 = Enable
Comp 4 = Enable
Comp 6 = Enable
Enable screens #3 and #4 require the manager password to change.
TGZ Units Only (R134a)
SET COMP SPs (5)
SET COMP SPs (5)
Expansion Valve
Expansion Valve
Type = Thermal
Type = Electronic
MaxOpPress=XXX.X psi
Exp
ansion Valve Type = Electronic
SET COMP SPs (6)
Cir 1 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Exp
ansion Valve Type = Electronic
SET COMP SPs (7)
Cir 2 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Exp
ansion Valve Type = Electronic Only
SET COMP SPs (8)
SuperheatTarg= XX.X
SET A
LARM LIMITS
SET ALARM LMTS (1)
Low EVAP Pressure
Hold=XXXpsi
Unload=XXXpsi
The Hold and Unload have the same default value of 59 psi. If two compressors are running, the
LowEvPrUnld is in effect and the lag compressor will be shut off to unload the unit. If one compressor is
running, the LowEvPrHold is in effect and the lag compressor is prevented from starting, thereby holding
the unit capacity.