www.DaikinApplied.com 35 IM 1240-4 • INTELLIGENT EQUIPMENT
11. Once created, set “ICMP hosts” of new interface to
“disable”
12. Under ‘Add New Interface to Monitor’, type “wan” in the
‘New Interface Name’ eld (Figure 77). Then, click the
‘Add New Interface’ button.
NOTE: Creating the “wan” interface eectively breaks the
cellular connection within the gateway’s conguration.
If the Intelligent Equipment installation subsequently
decides to switch to cellular for connectivity, then
the “wan” interface will need to be deleted within the
conguration screen.
13. Under ‘Priority Interface’, set to “wan”
14. Click ‘Save changes’ button
a. IMPORTANT: Allow the page to refresh
b. Conrm that there is number in parentheses next
to “Review Changes”. If so, proceed to step 12; if
not, repeat steps 8-11.
15. Remove ‘wwan’ interface
16. Remove ‘wlan0’ interface
17. Click the ‘Save Changes’ button
a. IMPORTANT: Allow the page to refresh
b. Conrm that there is number in parentheses next
to “Review Changes”. If so, proceed to step 15; if
not, repeat steps 8-14.
18. Click the ‘Apply Changes’ button in the lower right-hand
corner of the screen. The page will automatically refresh
when complete (this can take as much as two minutes).
19. Conrm that ‘ICMP host’ of “wan” interface is still set to
“disable”
a. If so, go to step 17.
b. If not, set to “disable”
c. Click ‘Save changes’ button
i. IMPORTANT: Allow the page to refresh
ii. Conrm that there is number in parentheses
next to “Review Changes”. If so, proceed to step
17; if not, repeat steps 8-16.
d. Click the ‘Apply Changes’ button in the lower
right-hand corner of the screen. The page will
automatically refresh when complete (this can take
as much as two minutes).
20. Click the ‘System’ tab, then click the Reboot button.
21. Reconnect the Ethernet cable between the M2M
Gateway and the MicroTech III controller. Procedure
complete.
NOTE: Be certain that the IT sta has allowed incoming and
outgoing internet trac on TCP ports 80, 443, 3197,
3199, 5222, 5223 and 8080.
It can take up to two hours for an initial push of all
unit data to the cloud.
Figure 75: M2M Gateway Home Page