VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
MG.90.D1.02 – VLT is a registered Danfoss trademark
45
Parameter list VLT 6000
Data
type
Conversion
index
PNU Parameter Factory setting Range Changes 4-Setup
# description during operation
001 Language English Yes No 0 5
002 Active Setup Setup 1 Yes No 0 5
003 Copying of Setups No copying No No 0 5
004 LCP copy No copying No No 0 5
005 Max value of user-defined readout 100.00 0 - 999.999,99 Yes Yes -2 4
006 Unit for user-defined readout No unit Yes Yes 0 5
007 Big display readout Frequency, Hz Yes Yes 0 5
008 Small display readout 1.1 Reference , Unit Yes Yes 0 5
009 Small display readout 1.2 Motor current, A Yes Yes 0 5
010 Small display readout 1.3 Power, kW Yes Yes 0 5
011 Unit of local reference Hz Yes Yes 0 5
012 Hand start on LCP Enable Yes Yes 0 5
013 OFF/STOP on LCP Enable Yes Yes 0 5
014 Auto start on LCP Enable Yes Yes 0 5
015 Reset on LCP Enable Yes Yes 0 5
016 Lock for data change Not locked Yes Yes 0 5
017 Operating state at power-up, Auto restart Yes Yes 0 5
local control
100 Configuration Open loop No Yes 0 5
101 Torque characteristics Automatic Energy Optimisation No Yes 0 5
102 Motor power, P
M,N
Depends on the unit 0.25-500 kW No Yes 1 6
103 Motor voltage, U
M,N
Depends on the unit 200 - 500 V No Yes 0 6
104 Motor frequency, f
M,N
50 Hz 24-1000 Hz No Yes 0 6
105 Motor current, I
M,N
Depends on the unit 0.01 - I
VLT,MAX
No Yes -2 7
106 Rated motor speed, n
M,N
Depends on 100-60000 rpm No Yes 0 6
par. 102 Motor power
107 Automatic motor adaptation, AMA Optimisation disable No No 0 5
108 Start voltage of parallel motors Depends on par. 103 0.0 - par. 103 Yes Yes -1 6
109 Resonance dampening 100 % 0 - 500 % Yes Yes 0 6
110 High break-away torque OFF 0.0 - 0.5 sec. Yes Yes -1 5
111 Start delay 0.0 sec. 0.0 - 120.0 sec. Yes Yes -1 6
112 Motor preheater Disable Yes Yes 0 5
113 Motor preheater DC current 50 % 0 - 100 % Yes Yes 0 6
114 DC braking current 50 % 0 - 100 % Yes Yes 0 6
115 DC braking time OFF 0.0 - 60.0 sec. Yes Yes -1 6
116 DC brake cut-in frequency OFF 0.0-par. 202 Yes Yes -1 6
117 Motor thermal protection ETR Trip 1 Yes Yes 0 5