Additional display readings
If a VLT is equipped with a PROFIBUS interface, it
can display the following readings in addition to the
messages described in the VLT 5000/5000 Flux/
6000 HVAC/8000 AQUA product manual:
Warnings
WARN. 34
PROFIBUS COMM. FAULT
There is no connection to the master. The reason
could be that the master has stopped (or is in
an error status), or that the PROFIBUS connec-
tion to the VLT is interrupted.
There is an SPM overflow in the FIFO buffer for
spontaneous messages.
(see ”Example of a spontaneous message”)
When parameters 927 and 928 are deacti-
vated, the ”Warning 34” in the display of the
VLT will also be suppressed.
Alarm conditions
ALARM
PROFIBUS OPT. FAULT
The option card has been destroyed by electri-
cal interference, or the option card is defective
and needs to be replaced.