MG.90.D1.02 – VLT is a registered Danfoss trademark
52
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
Parameter list VLT 8000 AQUA
Data
type
5
6
6
5
4
4
7
7
5
6
5
3
3
3
3
6
6
6
6
6
6
6
6
6
6
4
4
4
4
Conversion
index
0
-1
-1
0
-3
-3
0
0
0
-1
0
-2
-2
-2
-2
-1
0
-1
-1
-1
-1
-1
-1
-1
-1
-3
-3
-3
-3
Changes during operation:
"Yes" means that the parameter can be
changed, while the VLT AFD is in operation. "No"
means that the VLT AFD must be stopped before
a change can be made.
4-Setup:
"Yes" means that the parameter can be
programmed individually in each of the four
setups, i.e. the same parameter can have four
different data values. "No" means that the data
value will be the same in all four setups.
Conversion index:
This number refers to a conversion figure to be
used when writing or reading to or from a VLT
AFD by means of serial communication.
Conversion index Conversion factor
74 0.1
2 100
110
01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Text string
PNU Parameter Factory setting Range Changes 4-Setup
# description during operation
200 Output frequency range 0 -120 Hz 0 - 1000 Hz No Yes
201 Output frequency low limit, f
MIN
0.0 Hz 0.0 - f
MAX
Yes Yes
202 Output frequency high limit, f
MAX
60 Hz f
MIN
- par. 200 Yes Yes
203 Reference site Hand/Auto linked reference Yes Yes
204 Minimum reference, Ref
MIN
0.000 0.000-par. 100 Yes Yes
205 Maximum reference, Ref
MAX
60 Hz par. 100-999.999,999 Yes Yes
206 Ramp-up time Depends on the unit 1 - 3600 Yes Yes
207 Ramp-down time Depends on the unit 1 - 3600 Yes Yes
208 Automatic ramp-up/down Enable Yes Yes
209 Jog frequency 10.0 Hz 0.0 - par. 100 Yes Yes
210 Reference type Sum
1)
/Preset reference
2)
Yes Yes
211 Preset reference 1 0.00 % -100.00 - 100.00 % Yes Yes
212 Preset reference 2 0.00 % -100.00 - 100.00 % Yes Yes
213 Preset reference 3 0.00 % -100.00 - 100.00 % Yes Yes
214 Preset reference 4 0.00 % -100,00 - 100,00 % Yes Yes
215 Current limit, I
LIM
1.0 x I
VLT,N
[A] 0,1-1,1 x I
VLT,N
[A] Yes Yes
216 Frequency bypass, bandwidth 0 Hz 0 - 100 Hz Yes Yes
217 Frequency bypass 1 120 Hz 0.0 - par. 200 Yes Yes
218 Frequency bypass 2 120 Hz 0.0 - par. 200 Yes Yes
219 Frequency bypass 3 120 Hz 0.0 - par. 200 Yes Yes
220 Frequency bypass 4 120 Hz 0.0 - par. 200 Yes Yes
221 Warning: Low current, I
LOW
0.0 A 0.0 - par. 222 Yes Yes
222 Warning: High current, I
HIGH
I
VLT,MAX
Par. 221 - I
VLT,MAX
Yes Yes
223 Warning: Low frequency, f
LOW
0.0 Hz 0.0 - par. 224 Yes Yes
224 Warning: High frequency, f
HIGH
120.0 Hz Par. 223 - par. 200/202Yes Yes
225 Warning: Low reference, Ref
LOW
999,999.999 -999,999.999 - par. 226 Yes Yes
226 Warning: High reference, Ref
HIGH
999,999.999 Par. 225 - 999,999.999Yes Yes
227 Warning: Low feedback, FB
LOW
999,999.999 -999,999.999 - par. 228 Yes Yes
228 Warning: High feedback, FB
HIGH
999,999.999 Par. 227 - 999,999.999 Yes Yes
1) Sum = Global
2) Preset reference = North America
Parameter list