30 Manual RS8GL302 © Danfoss 2016-03 AK-CC 550B
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation
7=thermostat band changeover (activate r21). 8=alarm
function when closed. 9=alarm function when open.
10=case cleaning (pulse signal). 11=forced cooling at hot
gas defrost.). 12=night cover, 13=coordinated defrost).
15=appliance shutdown
o37 1 1 1 1 1 1 1 1 1 1 0 15 0
Conguration of light function: 1=Light follows day /night
operation, 2=Light control via data communication
via o39’, 3=Light control with a DI-input, 4=As "2", but
light switch on and night cover will open if the network
cut out for more than 15 minutes.
o38 1 1 1 1 1 1 1 1 1 4 1
Activation of light relay (only if o38=2) On=light
o39 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Rail heat On time during day operations
o41 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat On time during night operations
o42 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat period time (On time + O time)
o43 1 1 1 1 1 1 1 6 min. 60 min. 10
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All
output O.
*** o46 1 1 1 1 1 1 1 1 1 1 0 2 0
Selection of EL diagram. See overview page 12 and 13
* o61 1 1 1 1 1 1 1 1 1 1 1 10 1
Download a set of predetermined settings. See overview
page 27.
* o62 1 1 1 1 1 1 1 1 1 1 0 6 0
Access code 2 (partial access)
*** o64 1 1 1 1 1 1 1 1 1 1 0 100 0
Replace the controllers factory settings with the present
settings
o67 1 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Input signal on DI3. Function: (high voltage input)
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation,
7=thermostat band changeover (activate r21). 8=Not used.
9=Not used. 10=case cleaning (pulse signal). 11=forced
cooling at hot gas defrost, 12=night cover. 13=Not
used. 14=Refrigeration stopped (forced closing)).
15=appliance shutdown
o84 1 1 1 1 1 1 1 1 1 1 0 15 0
Rail heat control
0=not used, 1=pulse control with timer function (o41
and o42), 2=pulse control with dew point function
o85 1 1 1 1 1 1 1 0 2 0
Dew point value where the rail heat is minimum
o86 1 1 1 1 1 1 1 -10°C 50°C 8
Dew point value where the rail heat is 100% on
o87 1 1 1 1 1 1 1 -9°C 50°C 17
Lowest permitted rail heat eect in %
o88 1 1 1 1 1 1 1 0 % 100 % 30
Time delay from "open door refrigeration is started
o89 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Fan operation on stopped refrigeration (forced closing):
0 = Stopped (defrosting permitted)
1 = Running (defrosting permitted)
2 = Stopped (defrosting not permitted)
3 = Running (defrosting not permitted)
o90 1 1 1 1 1 1 1 1 1 1 0 3 1
Denition of readings on lower button:
1=defrost stop temperature, 2=S6 temperature, 3=S3
temperature , 4=S4 temperature
o92 1 1 1 1 1 1 1 1 1 1 1 4 1
Display of temperature
1= u56 Air temperature (set automtically to 1 at
application 9)
2= u36 product temperature
o97 1 1 1 1 1 1 1 1 1 1 1 2 1
Light and night blinds dened
0: Light is switch o and night blind is open when the
main switch is o
1: Light and night blind is independent of main switch
o98 1 1 1 1 1 1 1 1 1 1 0 1 0
Conguration of alarm relay
The alarm relay will be activated upon an alarm signal
from the following groups:
0 - Alarm relay not used
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
The groups that are to activate the alarm relay must be
set by using a numerical value which is the sum of the
groups that must be activated.
(E.g.: a value of 5 will activate all high temperature
alarms and all sensor error.
P41 1 1 1 1 1 0 127 111