EasyManua.ls Logo

Danfoss AK-PC 772A

Danfoss AK-PC 772A
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AK-PC 772A Capacity controller RS8HF102 © Danfoss 2017-07 79
5. Check Analog outputs
6. Put the control of the output voltage back to auto-
matic
Press the +-button to go on to the next page
7. Check Analog inputs
Definition Setting
0 % 50 % 100 %
0 - 10 V 0 V 5 V 10 V
1 - 10 V 1 V 5,5 V 10 V
0 - 5 V 0 V 2,5 V 5 V
2 - 5 V 2 V 3,5 V 5 V
Example of the connection between a defined output signal
and a manual set value.
Check that all sensors show sensible values.
In our case we have no values. This may be due to the following:
The sensor has not been connected.
The sensor is short-circuited.
The point or module number has not been set up correctly.
The configuration is not locked.
Set Control of output voltage to manual
Press in the Mode field.
Select MAN.
Press in the Value field
Select for example 50%.
Press OK.
On the output you can now measure the expected value: In this
example 5 volts
Check of connections - continued

Table of Contents

Related product manuals