8 DKRCI.PI.SC0.D2.02 / 520H5637 © Danfoss A/S (AC-SMC/MWA), 01-2012
Saturated vapour dielectric constant
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–40 → –35 –40 → –31 1.02
–34 → –26 –30 → –14 1.03
–25 → –19 –13 → –2 1.04
–18 → –14 –1 → 7 1.05
–13 → –9 8 → 16 1.06
–8 → –4 17 → 25 1.07
–3 → 0 26 → 32 1.08
1 → 3 33 → 38 1.09
4 → 6 39 → 43 1.10
7 → 9 44 → 49 1.11
10 → 12 50 → 54 1.12
13 → 15 55 → 59 1.13
R404A
Temperature range:
–40°C → +15°C (–40°F → +59°F)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–50 → –47 –58 → –52 1.01
–46 → –35 –51 → –31 1.02
–34 → –26 –30 → –14 1.03
–25 → –19 –13 → –2 1.04
–18 → –13 –1 → 9 1.05
–12 → –8 10 → 18 1.06
–7 → –4 19 → 25 1.07
–3 → 0 26 → 32 1.08
1 → 4 33 → 40 1.09
5 → 7 41 → 45 1.10
8 → 10 46 → 50 1.11
11 → 12 51 → 54 1.12
13 → 15 55 → 59 1.13
R410A
Temperature range:
–50°C → +15°C (–58°F → +59°F)
www.danfoss.com/ir
Default screen
• Press
• Press
• Press
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
DISTANCE
5000 mm
Enter password:
• Press
6 times
• Press
• Press
• Press
or
to see the language
possibilities
Press to conrm.
• Press 3 times
• Press
or
to select between
STORE NO or STORE YES.
Select STORE YES by pressing
Default screen appears:
Language setup completed
How to change the language setting (Default: English)
AKS 4100
QUICK SETUP ?
YES NO
Default screen
• Press
once and
twice
• Press
AKS 4100
DISTANCE
5000 mm
AKS 4100
DISTANCE
5000 mm
Enter password:
• Press
twice
• Press
• Press
• SelectYESbypressing
and conrm
with
• Press 3 times to return to default
screen.
Default screen appears:
Factory reset completed
Reset to factory setting
AKS 4100
3.0.0
SERVICE
AKS 4100
3.0.0
________