© Danfoss A/S (AC-SMC/MWA), 01-2012 DKRCI.PI.SC0.D2.02 / 520H5637 7
Default screen
• Press
• Press
• Press
Enter password:
AKS 4100
DISTANCE
5000 mm
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.5.0
APLICATION
AKS 4100
2.5.1
TRACING VEL.
• Press 4 times.
• Press
• Press 2 times.
• Press
to check/change GAS EPS.R.
(Select the correct value from the tables
below and on page 8)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
GAS EPS. R
1.066
AKS 4100
2.5.3
GAS EPS. R
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
• Press to conrm.
• Press 3 times.
• Press
or
to select between
STORE NO or STORE YES.
Select STORE YES by pressing
Default screen appears:
Entering the dielectric constant of
refrigerant gas completed
How to enter dielectric constant of refrigerant gas (all values below are only examples)
Optional Procedure
If the temperature condition in the stand pipe is known, a constant (dielectric constant of the refrigerant gas) can be entered (parameter
2.5.3 GAS EPS.R), in order to obtain lower Top and Bottom Dead Zone values (see g. 5).
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–40 –18 –40.0 0 1.01
–17 –5 1 23 1.02
–4 4 24 39 1.03
5 12 40 54 1.04
13 18 55 64 1.05
19 24 65 75 1.06
25 28 76 82 1.07
29 33 83 91 1.08
34 37 92 99 1.09
38 40 100 104 1.10
41 44 105 111 1.11
45 47 112 117 1.12
48 50 118 122 1.13
R717 (NH
3
)
Temperature range:
–40°C +50°C (–40°F +122°F)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–50.0 –42.0 –58.0 –43 1.01
–41.0 –28.0 –42 –18 1.02
–27.0 –17.0 –17 2 1.03
–16.0 –9.0 3 16 1.04
–8.0 –3.0 17 27 1.05
–2.0 2 28 36 1.06
3 7 37 45 1.07
8 11 46 52 1.08
12 14 53 58 1.09
15 59 1.10
R744 (CO
2
)
Temperature range:
–50°C +15°C (–58°F +59°F)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–50 –25.0 –58 –13 1.00
–24 –10 –12 14 1.02
–9 0 15 32 1.03
1 8 33 46 1.04
9 15 47 59 1.05
16 21 60 70 1.06
22 26 71 79 1.07
27 31 80 88 1.08
32 35 89 95 1.09
36 39 96 102 1.10
40 42 103 108 1.11
43 45 109 113 1.12
46 48 114 118 1.13
R22
Temperature range:
–50°C +48°C (–58°F +118°F)
Temperature
[°C]
Temperature
[°F]
Dielectric constant
of refrigerant gas
Parameter 2.5.3
GAS EPS.R
–40.0 –18 –40 –0 1.01
–17 –4 1 25 1.02
–3 5 26 41 1.03
6 13 42 56 1.04
14 20 57 68 1.05
21 25 69 77 1.06
26 30 78 86 1.07
31 34 87 94 1.08
35 38 95 100 1.09
39 42 101 108 1.10
43 45 109 113 1.11
46 48 114 119 1.12
49 50 120 122 1.13
R134a
Temperature range:
–40°C +50°C (–40°F +122°F)
Saturated vapour dielectric constant (default value: 1.066)
AKS 4100
1.0.0
QUICK START
AKS 4100
QUICK SETUP ?
YES NO

Other manuals for Danfoss AKS 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AKS 4100 and is the answer not in the manual?

Danfoss AKS 4100 Specifications

General IconGeneral
BrandDanfoss
ModelAKS 4100
CategoryAccessories
LanguageEnglish

Related product manuals