Quick Setup (all values below are only examples)
• Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press 3 times.
• Press
• Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D22 and press to conrm.
• Press
(NO) to conrm
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to conrm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to conrm.
• Press
or
to select between
STORE NO or STORE YES.
Press to conrm.
Default screen appears:
Quick Setup completed
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
1.0.0
QUICK START
Note:
The signal converter can be programmed with or without mechanical process connector assembled.
When used in NH
3
Default screen
• Press
• Press
• Press
Enter password:
AKS 4100
2.0.0
SUPERVISOR
AKS 4100
2.0.0
__________
AKS 4100
2.1.0
INFORMATION
AKS 4100
2.2.0
TESTS
AKS 4100
2.2.1
SET OUTPUT
AKS 4100
SET OUTPUT
3.5 mA
AKS 4100
SET OUTPUT
8 mA
• Press
• Press
• Press
• Press
to decrease the value or
to
increase the value.
Press to conrm.
• Press 4 times to return to default
screen.
Default screen appears:
Force mA completed and disabled
How to force mA output (all values below are only examples)
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE LENGTH
05000 mm
280 mm
AKS 4100
SCALE 4 mA
04946 mm
230 mm
AKS 4100
SCALE 20 mA
00070 mm
60 mm
AKS 4100
DISTANCE
5000 mm
250mm
AKS 4100
DISTANCE
5000 mm
250 mm
AKS 4100
DISTANCE
5000 mm
250 mm