© Danfoss | DCS (ADAP-KOOL®) | 2018.12
RI8SP202 | 7
1
“Reset alarm time” and “Relay rst enable”: These two parameters related to the alarm reset/acknowledge function are not accessible with the hand-
held tool.
2
The max alarm limit for CO2 is 16.000ppm / 80% of full scale. All other values equal the fullscale range of specific product
0: OK, Gas level below warning level
1: Warning, Gas level above warning level and delay expired
0 1 0 - Warning limit
Indication if the normal alarm function is inhibited or in normal
operation
0: Normal operation, i.e. alarms are created and cleared
1: Alarms inhibited, i.e. alarm status is not updated, e.g. due to DGS in
test mode
0 1 0 - Alarm inhibited
Critical Limit alarm
0: Alarm not active
1: Alarm, gas limit exceeded and delay expired
0 1 0 - 2:Criti. limit
0: OK
1: Fault. Out of range under test –Overrange or Underrange
0 1 0 - 2:Out of range
0: OK, sensor no errors
1: Fault, Sensor and Head failures
0 1 0 - 2:Wrong SensType
0: OK, sensor in place
1: Fault, Sensor out or removed, or wrong sensor placed in
0 1 0 - 2:Sens.removed
0: OK, Sensor not due for calibration
1: Warning, Due for calibration
0 1 0 - 2:Calibrate sens
0: OK, Gas level below warning level
1: Warning, Gas level above warning level and delay expired
0 1 0 - 2:Warning limit