MENU>Settings>Flow(boiler)temperature
DesiredT(Desiredflowtemperature)
1x004
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow
temperaturecanbeset.
A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU
>Settings>Returnlimit>'Con.T,ret.Tlim. '
SeeAppendix“ParameterIDoverview
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan
beappliedtoaninputinordertooverridetoComfort,Saving,Frost
ProtectionorConstanttemperature.Aslongasthecontact(switch)
signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
temp.max.
temp.min.
roomtemp.limit
returntemp.limit
flow/powerlimit
MENU>Settings>Flow(boiler)temperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview
Setthemin.duct/flow/inlettemperatureforthesystem.The
desiredduct/flow/inlettemperaturewillnotbelowerthanthis
setting.Adjustthefactorysetting,ifrequired.
Temp.min.isoverruledif'Totalstop'isactiveinSavingmodeor
'Cut-out'isactive.
Temp.min.canbeoverruledbytheinfluencefromthereturn
temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. hashigherprioritythan‘Temp.min. .
MENU>Settings>Flow(boiler)temperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview
Setthemax.flow/duct/inlettemperatureforthesystem.The
desiredtemperaturewillnotbehigherthanthissetting.Adjust
thefactorysetting,ifrequired.
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. hashigherprioritythan‘Temp.min. .