MENU>Settings>Tanktemperature
Stopdifference
1x194
OneDHWtanktemperaturesensor:
SetthenumberofdegreesaboveorbelowthedesiredDHWtemperature
thatwillstoptheDHWheating/charging.
TwoDHWtanktemperaturesensors:
SetthenumberofdegreesbelowthedesiredDHWtemperature,but
measuredbythelowertanktemperaturesensorthatwillstoptheDHW
heating/charging.
NOTE:Ifconditionforstop,relatedtothelowerDHWtanktemperature
sensor,ispresent,thestopisdonewhentheupperDHWtanktemperature
sensorhasatemperature2Khigherthanthestartdifferencelevel.
SeeAppendix“ParameterIDoverview
Value:
Setthenumberofdegrees.
OneDHWtanktemperaturesensor(examplewithpositive‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity
OneDHWtanktemperaturesensor(examplewithnegative‘Stop
difference’value):
X
=
Time
#1#
=
Stopdifference(ID1x194)
#2#
=
DesiredDHWtemperature
#3#
=
ActualDHWtemperature
#4#
=
DHWheating/chargingactivity