MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
1x085
Choosewhetherthereturntemperaturelimitationshouldoverruletheset
min.flowtemperature‘Temp.min. .
SeeAppendix“ParameterIDoverview
OFF:
Themin.flowtemperaturelimitisnotoverruled.
ON:
Themin.flowtemperaturelimitisoverruled.
IfyouhaveaDHWapplication:
Pleasealsosee‘Paralleloperation(ID11043).
IfyouhaveaDHWapplication:
Whendependentparalleloperationisinfunction:
Desiredflowtemperaturefortheheatingcircuitwillbeminimum
limited,when"Priorityforreturntemperature"(ID1x085)isset
toOFF.
Desiredflowtemperaturefortheheatingcircuitwillnotbe
minimumlimited,when"Priorityforreturntemperature"
(ID1x085)issettoON.
120|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375