MENU>Settings>Boiler
Max.Tlimit
1x049
A275applications:
Iftheboiler/flowtemperatureexceedsthesetvalue,theburneriscut-out.
A375applications:
Iftheboiler/flowtemperatureexceedsthesetvalue,burnerstepsare
cut-outinintervalsof5sec.
SeeAppendix“ParameterIDoverview
40...150:
Setthelimitationtemperature.
'Max.Tlimit'overrules'Min.ONtime' .
MENU>Settings>Boiler
Min.ONtime
1x071
Settheminimumoperationtime(minutes)fortheburner.
SeeAppendix“ParameterIDoverview
1...9m:
Theboilercanbeprotectedagainstcondensation/
corrosioncausedbyinsufficientheat-uptimeateach
burnerstart.Theprotectionisobtainedbyaminimum
operationtimeoftheburner.Withthissettingtheboiler
temperaturedifference(IDno.11046‘Difference’)is
overruled.
'Min.ONtime'isoverruledby'Max.Tlimit'.
VI.GU.L2.02
©Danfoss|2017.09|129
OperatingGuideECLComfort210/296/310,applicationA275/A375