5.10.2Temp.monitor.
MENU>Settings>Alarm
Upperdifference
1x147
Thealarmisactivatediftheactualflow/ducttemperatureincreasesmore
thanthesetdifference(acceptabletemperaturedifferenceabovethedesired
flow/ducttemperature).Seealso'Delay'.
SeeAppendix“ParameterIDoverview
OFF:
Therelatedalarmfunctionisnotactive.
Value:
Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
Upperdifference
X
=
Time
Y
=
Temperature
#1#
=
Upperdifference
#2#
=
Desiredflowtemperature
MENU>Settings>Alarm
Lowerdifference
1x148
Thealarmisactivatediftheactualflow/ducttemperaturedecreasesmore
thanthesetdifference(acceptabletemperaturedifferencebelowthedesired
flow/ducttemperature).Seealso'Delay'.
SeeAppendix“ParameterIDoverview
OFF:
Therelatedalarmfunctionisnotactive.
Value:
Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
Lowerdifference
X
=
Time
Y
=
Temperature
#1#
=
Lowerdifference
#2#
=
Desiredflowtemperature
VI.GU.L2.02
©Danfoss|2017.09|151
OperatingGuideECLComfort210/296/310,applicationA275/A375