ECAMENU>ECAsystem>ECAdisplay
Contrast(displaycontrast)
Settingrange
Factorysetting
0...103
Adjustthecontrastofthedisplay.
0:
Lowcontrast.
10:
Highcontrast.
ECAMENU>ECAsystem>ECAdisplay
Useasremote
Settingrange
Factorysetting
OFF/ON*)
ECA30/31canactasasimpleornormalremote
controlfortheECLcontroller.
OFF:
Simpleremotecontrol,noroomtemperaturesignal.
ON:
Remotecontrol,roomtemperaturesignalisavailable.
*):
Differently,dependingonchosenapplication.
WhensettoOFF:TheECAmenushowsdateandtime.
WhensettoON:TheECAmenushowsdateandroomtemperature
(andforECA31relativehumidity).
ECAMENU>ECAsystem>ECAcommunication
Slaveaddr.(Slaveaddress)
Settingrange
Factorysetting
A/B
A
Thesettingof'Slaveaddr. 'isrelatedtothesetting
'ECAaddress'intheECLcontroller.
IntheECLcontrolleritisselectedfromwhichECA30
/31unittheroomtemperaturesignalisreceived.
A:
TheECA30/31hastheaddressA.
B:
TheECA30/31hastheaddressB.
ForinstallationofanapplicationinanECLComfort210/296/310
controllerthe'Slaveaddr.'mustbeA.
IftwoECA30/31areconnectedinthesameECL485bussystem,the
'Slaveaddr.'mustbe"A"intheoneECA30/31unitand"B"intheother.
VI.GU.L2.02
©Danfoss|2017.09|175
OperatingGuideECLComfort210/296/310,applicationA275/A375