A275.2,examplea
BoilerON/OFFcontrolforaheatingandaDHWcircuit.OptionalDHWpriority.
*=pressurereliefvalve
AtDHWheatingP3isswitchedONandthedesiredboilertemperatureliesanumberofdegreesabovethedesiredDHWtemperature.
P1isswitchedOFF.
SpecialsettingsfortypeA275.2,examplea:
Navigation:
IDno.:
Recommendedsetting:
DHWcircuit(circuit2)
DHWheatingismanagedbypumpP3:
MENU\Settings\Application:'Ch.-o.valve/P'
12051
ON
ThedesiredDHWheatingtemperaturemustinfluencethedesiredboilertemperature:
MENU\Settings\Application:Tank,sec./prim.'
12053
OFF
Pleasenote:
If'Ch.-o.valve/P'in12051issettoOFF,P3willbeswitchedonatDHWheating.Thedesiredboilertemperaturewillstillliea
numberofdegreesabovethedesiredDHWtemperatureandP1willremainswitchedON.