A275.2,examplec
BoilerON/OFFcontrolforaheatingandaDHWcircuit.OptionalDHWpriority.Theboilercircuitisequippedwithalowlossheader.
*=pressurereliefvalve
Thepumpintheboilercircuitisnotcontrolled.
AtDHWheatingP3isswitchedONandthedesiredboilertemperatureliesanumberofdegreesabovethedesiredDHWtemperature.
P1isswitchedOFF.
SpecialsettingsfortypeA275.2,examplec:
Navigation:
IDno.:
Recommendedsetting:
DHWcircuit(circuit2)
DHWheatingismanagedbypumpP3:
MENU\Settings\Application:'Ch.-o.valve/P'
12051
ON
ThedesiredDHWheatingtemperaturemustinfluencethedesiredboilertemperature:
MENU\Settings\Application:Tank,sec./prim.'
12053
OFF
Pleasenote:
If'Ch.-o.valve/P'in12051issettoOFF,P3willbeswitchedonatDHWheating.Thedesiredboilertemperaturewillstillliea
numberofdegreesabovethedesiredDHWtemperatureandP1remainswitchedON.
VI.GU.L2.02
©Danfoss|2017.09|23
OperatingGuideECLComfort210/296/310,applicationA275/A375