A375.1,examplec
Oneboilerwith2xburnerON/OFFcontrolforaheatingcircuit.Theboilercircuitisequippedwithalowlossheader.
*=pressurereliefvalve
Thepumpintheboilerisnotcontrolled.
Fixedsequence:Burner1mustbeswitchedONbeforeburner2canbeswitchedON
Burner1isactiveatlowheatdemand.Atincreasedheatdemandburner2isactivatedadditionally.
Thelastburnerstepcanbedisablediftheoutdoortemperatureishigherthanasetvalue.
SpecialsettingsfortypeA375.1,examplec:
Navigation:
IDno.:
Recommendedsetting:
Heatingcircuit(circuit1)
Sequencetype(code)forcontrollingtheburners:
MENU\Settings\Boiler:'Sequencetype'
110723
Numberoftotalburnersteps:
MENU\Settings\Boiler:‘Steps'
110732
34|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375