ApplicationKey:Situation2
Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the
currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Examples:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
ChooseCommoncontrollersettings
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication
Confirmwith‘Yes
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
78|©Danfoss|2017.09
VI.GU.L2.02
OperatingGuideECLComfort210/296/310,applicationA275/A375