Instructions ECL Comfort 210 / 310, communication description
"PNU offset" Type 2 Type 3
0
Address Address
1
Type Type
2
Scan time Scan time
3
ID / Serial ID / Serial
4
- low part - low part
5
Reserved Reserved
6 Flow temp. [0,01 °C] Flow temp. [0,01 °C]
7 Return temp. [0,01 °C] Return temp. [0,01 °C]
8 Flow [0,1 l/h] Flow [0,1 l/h]
9 - low - low
10 Power [0,1 kW] Power [0,1 kW]
11 - low - low
12 Acc. Volume [0,1 m3] Acc. Volume [0,1 m3]
13 - low - low
14 Acc. Energy [0,1 kWh] Acc. Energy [0,1 MWh]
15 - low - low
16 Tariff1 Acc. Energy [0,1 kWh] Tariff1 Acc. Energy [0,1 MWh]
17 - low - low
18 Tariff2 Acc. Energy [0,1 kWh] Tariff2 Acc. Energy [0,1 MWh]
19 - low - low
20 Up time [d] Up time [d]
21 Current time [m-bus defined structure] Current time [m-bus defined structure]
22 - low - low
23 Error status [heat meter defined bitmask] Error status [heat meter defined bitmask]
24
Danfoss District Energy VI.LG.V3.02 DEN-SMT/DK