InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Settings>Application
Accum.lter(Accummulationlter)
1x082
CircuitSettingrange
Factorysetting
All
**
Thevaluedeterminesthelteringofthedesiredow/ducttemperaturein
ordertochangecorrectlyfromheatingtocoolingmodeorviceversa.
Thesetvalueisanindirecttimeconstant.Theresultingtimeconstantis
listedintheexamplesbelow.

Lowvalue:
Highvalue:




















Duct/roomtemp.
Deadzone(IDno.
11009)
Heating
°C
Cooling
Actual
Dampened


MENU>Settings>Application
Frostpr.T(frostprotectiontemp.)
1x093
CircuitSettingrange
Factorysetting
All
**
SetthedesiredowtemperatureattemperaturesensorS3toprotectthe
systemagainstfrost(atheatingcut-out,totalstopetc.).
WhenthetemperatureatS3getslowerthanthesetting,themotorized
controlvalveopensgradually.





