InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Alarm>Temp.monitor
Upperdifference
1x147
CircuitSettingrange
Factorysetting
All
**
Thealarmisactivatediftheactualow/ducttemperatureincreasesmore
thanthesetdifference(acceptabletemperaturedifferenceabovethedesired
ow/ducttemperature).Seealso'Delay'.
OFF:
Value:
Flow/ducttemp.°C
Upperdifference(set
value)
Desiredow/duct
temp.
Time
MENU>Alarm>Temp.monitor
Lowerdifference
1x148
CircuitSettingrange
Factorysetting
All
**
Thealarmisactivatediftheactualow/ducttemperaturedecreasesmore
thanthesetdifference(acceptabletemperaturedifferencebelowthedesired
ow/ducttemperature).Seealso'Delay'.
OFF:
Value:
Flow/ducttemp.°C
Lowerdifference(set
value)
Desiredow/duct
temp.
Time
MENU>Alarm>Temp.monitor
Delay
1x149
CircuitSettingrange
Factorysetting
All
**
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is
presentforalongertimethanthesetdelay(inminutes),thealarmfunction
isactivated.
Value:
Temp.
Flowtemp.
Alarmlimit
Time
Delay
MENU>Alarm>Temp.monitor
Lowesttemp.
1x150
CircuitSettingrange
Factorysetting
All
**
Thealarmfunctionwillnotbeactivatedifthedesiredow/duct
temperatureislowerthanthesetvalue.