InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Alarm>Frostthermostat
Alarmvalue
1x616
CircuitSettingrange
Factorysetting
All
**
Afrostthermostatcanbeconnectedtothefrostthermostatsensorinput.
Whenthetemperature,measuredbythefrostthermostat,getsbelowtheset
value,theS7inputwillbeactivated.
Thefrostalarmcanbeactivatedwhenthecontactsinthefrostthermostat
openorclose.
0:
1:
MENU>Alarm>Airquality
MENU>Alarm>Frostthermostat
MENU>Alarm>Heatrecovery
MENU>Alarm>Inletpressure
MENU>Alarm>Outletpressure
Alarmtime-out
1x617
CircuitSettingrange
Factorysetting
All
**
Thealarmisactivatedwhenthealarmreasonhasbeenpresentforalonger
time(inseconds)thanthesetvalue.
Value:
MENU>Alarm>Firesafety
Alarmvalue
1x636
CircuitSettingrange
Factorysetting
All
**
ArethermostatcanbeconnectedtotheS8input.Whenthetemperature,
measuredbytherethermostat,getsabovethesetvalue,theS8inputwill
beactivated.
Therealarmcanbeactivatedwhenthecontactsintherethermostat
openorclose.
0:
1: