InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Alarm>FrostT
Alarmvalue
1x676
CircuitSettingrange
Factorysetting
All
**
Whentheactualtemperature,measuredbyS6,getsbelowthesetvalue,the
frostalarmwillbeactivated.
Value:
MENU>Alarm>DigitalS10
Alarmvalue
1x696
CircuitSettingrange
Factorysetting
All
**
AdifferentialpressureswitchcanbeconnectedtotheS10input.Whenthe
differentialpressure,measuredbythedifferentialpressureswitch,gets
abovethesetvalue,theS10inputwillbeactivated.
Thealarmcanbeactivatedwhenthecontactsinthedifferentialpressure
switchopenorclose.
0:
1:
MENU>Alarm>DigitalS10
Alarmtime-out
1x697
CircuitSettingrange
Factorysetting
All
**
Thealarmisactivatedwhenthealarmreasonhasbeenpresentforalonger
time(inseconds)thanthesetvalue.
Value: