Setup & service menu (Requires Log-In. Password to be assigned in Commisioning menu) - Continued
Parameter Options
User level - access
Default
valuesDaily Service Commissioning
Service Controller state R R R -
Actual level R R R (D) -
Actual referrence R R R (D) -
Actual OD R R R (D) -
Actual valve position R R R (D)
Digital input status R R R (D) -
Actual level signal voltage R R R (D)
Actual level signal current R R R (D) -
Actual position signal
voltage
R R R (D)
Actual position signal
current
R R R (D)
Actual OD A R R R (D)
Actual OD B R R R (D)
Actual OD C R R R (D)
Manual Mode On, O R RW RW (D) Off
Manual OD 0 - 100% R RW RW (D) 50.0%
Manual low alarm Off-On R RW RW (D) Off
Manual high alarm Off-On R RW RW (D) Off
Manual common alarm Off-On R RW RW (D) On
Apply defaults None, Factory N/A N/A RW (D) None
Setup wizard Setup wizard Re-run Setup wizard N/A N/A RW -
I/O check Main switch EKE act: Off - On R R R Off
AKS 4100 EKE act: 0 - 20 mA R R R (D) -
ICAD EKE act: 4 - 20 mA R R R (D) -
Nor. Close (NC) EKE act:
Off - On R R R (D) -
Upper lvl (alarm) EKE act: Off - On R R R (D) -
Lower lvl (alarm) EKE act: Off - On R R R (D) -
Controller
name
Controller name Type in controller name RW RW RW -
RW = Read & Write R = Read only N/A = Not shown (L) = Locked by Mainswitch ( Switch OFF Mainswitch for change of setting)
(D) = Parameter is hidden if not active in the selected application