Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
2 step mode 2: Open &
close;
1: Close;
0: Open
Only active if 2 step mode
(ID158) is set to 0 (Open) or 2
(Open & close)
The valve will stop in this
position before moving to
the fully open (100%) posi-
tion 0…75% (min step – 1%)
Only active if 2 step mode
(ID158) is set to 1 (Close) or 2
(Open & close)
The valve will stop in this
position before moving to
the fully closed (0%) position
0…75% (min step – 1%)
Only active if 2 step mode
(ID158) is set to 0 (Open) or 2
(Open & close) 5…600 sec-
onds (min step – 1)
Only active if 2 step mode
(ID158) is set to 1 (Close) or 2
(Open & close) 5…600 sec-
onds (min step – 1)
Enable/Disable forced
closing Not active when
CVE valve is chosen (ID8)
1: On: When valve Opening
Degree < 3% it will be forced
to close regardless of re-
quested ICM valve Opening
Degree
0: O: When valve Opening
Degree < 3% no forced clos-
ing will take place. Disa‐
bling forced closing is not
recommended as it can
lead to leaking valves.
ICAD indicates in display
when calibration is taking
place. Calibration is carried
out as part of the boosting
process when the requested
opening degree cannot be
reached based on settings in
ID28. Calibration is also per-
formed after the selection of
a valve (ID8)
2: Extended: Calibration
from fully closed to fully
open
1: Normal: Forced calibra-
tion to fully closed
0: None: No calibration per-
formed
Selection of startup cali‐
bration type
1: Extended: Calibration
from fully closed to fully
open
0: Normal: Forced calibra-
tion to fully closed
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 21
ICM and ICMTS Motorized Valves with ICAD Actuators