MCD 200 Design Guide
14 MG.17.C3.02 – VLT is a registered Danfoss trademark
MCD 201
Description of choice:
Set the ramp time to optimise stopping characteristics
for the load.
Indication
LED OFF ON FLASH
Ready No control
power
Ready Starter
tripped
Run Motor not
running
Motor
running at
full speed
Motor
starting or
stopping
Fault Finding
Ready LED Description
x 1
Power Circuit Fault:
Check mains supply L1, L2 & L3,
motor circuit T1, T2 & T3 and soft
starter SCRs.
x 6
Supply Frequency:
Check supply frequency is in range
x 8
Network Comms Failure (between
accessory module and network):
Check network connections and
settings.
x 9
Starter Comms Failure (between starter
and accessory module): Remove and
refit accessory module.