Instructions
2 | AN23018649735402-000601 - 8510196P04J
© Danfoss | DCS (CC) | 2021.02
The compressor must only be used for its
designed purpose(s) and within its scope of
application (refer to «operating limits»).
Consult Application guidelines and data-
sheet available from cc.danfoss.com
The compressor is delivered under
nitrogen gas pressure (between 0.3
and 0.7 bar) and hence cannot be
connected as is; refer to the «assembly»
section for further details.
Under all circumstances, the
EN378 (or other applicable local safety
regulation) requirements must be
fullled.
The compressor must be handled
with caution in the vertical position
(maximum oset from the vertical :
15°)
Refrigerant Oil
MT MTZ VTZ NTZ
R22 R417A* R407A** R407C R407F** R134a
R404A /
R507
R452A R448A R449A R513A
R454C***R455A***
R407C R134a
R404A/
R507
R452A R454C***
R455A***
R404A/
R507
160P 175PZ 175PZ 160PZ 175PZ
High side
pressure range
bar (g)
10.9 -
27.7
9.32 -
25.5
11.6 -
25.8
12.5 -
29.4
12.1 -
24.0
7.87 -
22.6
13.2 -
27.7
12.5 -
27.3
11.7 -
26.0
11.7 -
25.9
8.37 -
23.36
5.2 -
22.3
5.6 -
24.3
7.8 -
29.4
7.87 -
20.2
9.89 -
27.7
12.5 -
24.2
5.2 -
22.3
5.6 -
24.3
13.2 -
27.7
Low side
pressure range
bar (g)
1.01 -
6.89
0.54 -
5.66
0.53 -
5.94
1.43 -
6.55
0.99 -
6.25
0.06 -
4.72
1.04 -
7.2
0.84 -
6.69
0.6 -
6.08
0.6 -
6.07
0.21 -
5.12
0.4 -
5.2
0.5 -
5.6
1.43 -
6.55
0.64 -
3.88
1.04 -
6.06
0.18 -
2.99
0.05 -
2.2
0.12 -
2.4
0.05 -
3.34
Discharge temperature must be kept lower than 130°C
* When MT compressors are used with R417A, the factory charged mineral oil 160P must be replaced by polyolester oil 175PZ.
** R407A and R407F are not used for China Market.
*** MTZ18/22/28/32/36/40 and NTZ048/068 in voltage 380-400 3~ 50Hz / 460V 3~ 60Hz / 220-240V 1~ 50Hz
175PZ
A
B
C
D
E
F
1" : 80 Nm
1"1/4 : 90 Nm
1"3/4 : 110 Nm
Installation and servicing of the compressor by qualied personnel only. Follow these instructions and sound refrigeration engineering practice relating to
installation, commissioning, maintenance and service.
C
R
S
IOL
230 V
RC
TH
C
S
R
IOL
1 ~ PSC
1
~ CSR
230 V
SR
5
2
1
C
S
R
IOL
TH
RC
SC
C
R
S
Never operate compressors without
terminal cover tted
A: Model number D: Supply voltage, Starting current & Maximum current
B: Serial number E: Housing service pressure
C: Certication logo: Contact Danfoss F: Factory charged lubricant
TH : Thermostat SR : Start Relay
SC : Start Capacitor RC : Run Capacitor
IOL : Motor Protector
HM8-40
15 Nm
15 Nm
HM12-50
Danfoss reciprocating compressors
MT / MTZ / NTZ / VTZ

Related product manuals