Optyma Plus
TM
User Guide RS8GD602 © Danfoss 2015-10 17
Data
Supply voltage 230 V a.c. +10/-15 %. 5 VA, 50 Hz
Sensor S2, S3,
S4, S5,
Pt 1000
Accuracy
Measuring range
-60 to +120°C
(S3 to 150°C)
Controller
±1 K below -35°C
± 0.5 K between -35 to +25°C;
±1 K above +25°C
Pt 1000 sensor
±0.3 K at 0°C
±0.005 K per grad
Measuring of
Pc, Ps
Pressure trans-
mitter
Ratiometric. eg. AKS 32R
Display LED, 3-digits
External display EKA 163B or 164B (any EKA 163A or 164A)
Digital inputs
DI1, DI2
Signal from contact functions
Requirements to contacts: Gold plating
Cable length must be max. 15 m
Use auxiliary relays when the cable is longer
Digital input DI3 230 V a.c. from safety pressostat. Low/high pressure
Electrical con-
nection cable
Max.1.5 mm
2
multi-core cable
Triac output
Fan
Max. 240 V a.c. , Min. 28 V a.c.
Max. 2.0 A
Leak < 1 mA
Relays*
CE
(250 V a.c.)
Comp, CCH 4 (3) A
Alarm, Fan, Aux 4 (3) A
Analog output
2 pcs. 0-10 V d.c.
(For external speed control of fans and compressors)
Min. load = 10 K ohm. (Max. 1 mA)
Environments
-25 to +55°C, During operations
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock inuence / vibrations
Density IP 20
Mounting DIN-rail or wall
Weight 0.4 Kg
Data communi-
cation
Fixed MODBUS
Extension options LON
Power reserve
for the clock
4 hours
Approvals
EC Low Voltage Directive and EMC demands re CE-
marking complied with
LVD tested acc. EN 60730-1 and EN 60730-2-9, A1, A2
EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
* Comp and CCH are 16 A relays. Alarm and Fan are 8 A relays. Max. load must be observed
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such as LEDs and on/o
control of EC motors.
All loads with a switch mode power supply must be connected with a suitable contactor or simi-
lar.