VL 2800 Series
even further, a Recidual Current Device (RCD) can be
fitted to ensure that the adjustable frequency drive
cuts out when the leakage currents get too high. Also
see RCD Application note MN.90.GX.02.
Load sharing
Load sharing provides the facility to connect several
frequency converters DC intermediate circuits.
This requires that the installation is extended using
extra fuses and AC coils (see drawing below).
For load sharing parameter 400 Brake function
must be set to Load sharing [5].
Use 6.3 mm Faston Plugs for DC (Load Sharing).
Contact Danfoss or see instructions no. MI.50.NX.02
for further information.
No. 88 89 Loadsharing
-+
Note that voltage levels of up to 850 V DC
may occur between terminals 88 and 89.
Tightening Torque, Power Terminals
Power and ground terminals must be tightened
with the following torques:
VLT Terminals To rq ue [ N m]
Power line brake 0.5-0.62803-
{new-
line/}2875
Ground 2-3
Power line brake 1.2-1.52880-
{new-
line/}2882
Ground 2-3
Calculation of brake resistance
In lifting/lowering applications you need to be able
to control an electromagnetic brake. The brake is
controlled using a relay output or digital output (terminal
46). The output must be kept closed (voltage-free)
for the period of time during which the variable
frequency drive is not able to support the motor,
for example due to the load being too great. Select
Mechanical brake control in parameter 323 or 341 for
applications with an electromagnetic brake.
When the output frequency exceeds the brake cut
out value set in par. 138, the brake is released if the
motor current exceeds the preset value in parameter
140. When stopping the brake is engaged when the
output frequency is less than the brake engaging
frequency, which is set in par. 139.
If the variable frequency drive is placed at alarm
status or in an overvoltage situation the mechanical
brake is cut in immediately.
NOTE
This application is only for lifting/lowering
without a counterbalance.
Access to control terminals
All control terminals are located underneath the
protective plate on the front of the adjustable
frequency drive. Remove the protective plate by
sliding it downwards (see drawing).
MG.28.A8.22 - VLT is a registered Danfoss trademark
18

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
Frequency50/60 Hz
Communication OptionsRS-485, Profibus DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Enclosure RatingIP20
Storage Temperature-25 to +65°C
Relative Humidity5 - 95% RH, non-condensing
AltitudeUp to 1000m above sea level