EasyManuals Logo

Danfoss VLT 2800 Series Manual

Danfoss VLT 2800 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
VL 2800 Series
Installation
Electrical installation, control circuitry
NOTE
Using unshielded/unarmored cable may not
comply with some EMI/RFI requirements.
Control wires must be shielded/armored. Connect the
shield to the drive chassis with a clamp. Normally,
the shield must also be connected to the chassis of
the controlling device. (See the instructions for the
specific device.) In analog signals or connections using
very long wires, 50/60 Hz ground loops may occur
because of noise transmitted from the AC line. It may
be necessary to break the shield and insert a 100 µF
capacitor between the shield and the chassis.
MG.28.A8.22 - VLT is a registered Danfoss trademark
19

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
Frequency50/60 Hz
Communication OptionsRS-485, Profibus DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Enclosure RatingIP20
Storage Temperature-25 to +65°C
Relative Humidity5 - 95% RH, non-condensing
AltitudeUp to 1000m above sea level

Related product manuals