If Active [1] is selected, the user-defined Quick Menu
is active.
025 Quick Menu setup
(quick menu setup)
Value:
[Index 1 - 20] Value: 0 - 999
000
Function:
In this parameter you define which parameters are re-
quired in the Quick Menu when parameter 024 User-
defined Quick Menu is set to Active [1].
Up to 20 parameters can be selected for the user-de-
fined Quick Menu.
NB!
Please note that this parameter can only
be set using an LCP 2 control panel. See
Order form.
Description of choice:
The Quick Menu is set up as follows:
1.
Select parameter 025 Quick Menu setup and
press [CHANGE DATA].
2. Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index
numbers using the [+ / -] keys. Select Index
1.
3. Using [< >] you can scroll between the three
figures. Press the [<] key once ad the last
number in the parameter number can be se-
lected using the [+ / -] keys. Set Index 1 to
100 for parameter 100 Configuration.
4. Press [OK] when Index 1 has been set to 100.
5. Repeat steps 2 - 4 until all parameters re-
quired have been set to the Quick Menu key.
6. Press [OK] to complete the Quick Menu set-
up.
If parameter 100 Configuration is selected at Index 1,
Quick Menu will start with this parameter every time
Quick Menu is activated.
Please note that parameter 024 User-defined Quick
Menu and parameter 025 Quick Menu setup are reset
to the factory setting during initialisation.
VLT
®
2800 Series
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark 17
Programming