EasyManua.ls Logo

Danfoss VLT 5202 - Technical Data; General Technical Data

Danfoss VLT 5202
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VL 5000 Crane
General Technical Data
Mains Supply (L1, L2, L3)
Supply voltage 400 - 500 V units 3 x 400/415/440/460/500 V ± 10%
Supply frequency 50/60 Hz ± 1%
Max. imbalance of supply voltage
VLT 5052 - 5062/400 - 500 V
VLT 5072 - 5202/400 - 500 V
of rated supply voltage
1.5%
3%
Power factor/cos ϕ
1
0.90/1 at rated load
No. of switches on supply input L1, L2, L3 Appr. 1 time/minute
Max. short-circuit rating 100.000 A
VLT Data Output (U, V, W)
Output voltage 0-100% of supply voltage
Output frequency 0-160 Hz
Rated motor voltage 400 - 500 V units 315 V
Rated motor frequency 25/37 Hz
Ramp times 0.05 - 3600 Seconds
Torque Characteristics
Starting torque, VLT 5042–5202, 400 - 500 V 160%
for 1 minute
Acceleration torque, VLT 5042–5302, 400 - 500 V 160%
for 1 minute
Overload torque, VLT 5042-5302, 400 - 500 V 160%
for 1 minute
Holding torque at 0 rpm (closed loop), VLT 5042–5302, 400 - 500 V 160%
for 1 minute
Digital Inputs
Number of digital inputs 9
Voltage level 0-24 V DC (PNP positive logics)
Voltage level, logical 0 <5 V DC
Voltage level, logical 1 >10 V DC
Max. voltage on input 28 V DC
Input resistance, R
i
(terminal 29) Appr. 4 K /2 K (2 K )
Scanning time per input 3msec
NOTE: All digital inputs are galvanic isolated from the mains voltage (PELV). In addition, the digital inputs can be isolated from the other
terminals on the control card by connecting an external 24 V DC supply and opening switch 4, see Electrical installation.
Analogue Inputs
Number of programmable analogue voltage inputs/thermistor inputs 1
Voltage level 0- ± 10 V DC (Scalable)
Input resistance, R
i
Appr. 10 K
Number of programmable analogue current inputs 2
Current range 0/4- 20 mA (Scalable)
Input resistance, R
i
200
Resolution 10 + sign bit
Accuracy on input Max. error: 1% of full scale
Scanning time per input 3msec
NOTE: Analogue inputs are galvanic isolated from the mains voltage (PELV) and functionally isolated from all other inputs
MG.50.N4.02 - VLT is a registered Danfoss trademark
16

Other manuals for Danfoss VLT 5202

Related product manuals